Design Solar Plant For House and offices by itself (Understanding Purpose, not Practical)



KISSAN  SOLAR EDUCATION



CALCULATE RATING of Solar's Equipment : Are Your Looking for SOLAR DESIGN for your Home, Offices by Itself ?




Energy Flow Diagram in a Solar System for Home, Offices

To know Rating of Each equipment , you should calculate from Reverse Direction of Energy Flow Diagram.

Step 1 : Calculate Load Requirement : Number of load you want to run from Solar.



Important Calculation  

1. Total wattage of Load  : (watt * quantity ) =  9*2 + 60*1 +150*1 . . . . . +250*1 =628 Watt 
2. Total Energy Consumed By load : (wattage * number . of hour used) =  9*5*2 + 60*8*1 + .......+ 250*3*1 = 2820 Wh

Step 2 : Find out Size of Inverter ,

                        

Important :  
Output Energy of Load  = 2820 wh

We need to find out Rating of inverter and  Input of Inverter or output of Battery : 
Every inverter has Efficiency mentioned by manufacturer : 90% to 95 %. Let take 93 %



Rating of Inverter = Total wattage at output need = 628 VA = 650 W inverter

Step 3 : Size of Battery : 




To find Size of Battery, we need two Important Parameter of Battery 
1. DoD ( Depth of Discharge)
2. Efficiency of Battery


Depth of Discharge : This indicates how much charge you can take from battery for reliable operation and life of battery. Ex if DoD is 70%, you can discharge 70 %  of battery, after 70%, it is recommendation to re charge quickly the battery .
Lead Acid battery has 50% DoD
Excide Battery has 80% DoD







You can also consider Autonomy i.e no. of days do you want to keep charge storage in battery.

For 2 days, total charge required,  total rating of battery need = 3 * 381 = 1143 Ah


Step 4 : Size of Charge controller and MPPT : 





Here, Input energy of Battery is considered 4566 Wh, but according to problems it must 3653Wh.

Step 5 : To find out Rating of Panel , No. of Panel :



In Every area there is given peak hour of sunshine i.e. number of hours sunshine become maximum, 
You can find this from google

if you are in Saket, Delhi =  

Annual Average : 4.33 kWh/m2/day

If you are in Ranchi jharkhand 

Annual Average : 5.15 kWh/m2/day







Here Size of Charge controller will 12 V, 82A


Assignment Question :  

Comments

Post a Comment

Join Kissan Education for Deeply knowledge on Solar System Design

Visit : www.kissanedu.com

Popular posts from this blog

Assignment 2: Design a Off Grid Solar System For Your Home

KISSAN EDUCATION www.kissanedu.com You are going to install a solar power system in our home for a total load of 800W where the required backup time of the battery is 3 hours. Optimize it. If you are living in Kolkata, West Bangla. Find out Charging Current for Battery . Take Solar Inverter, efficiency = 95% ( Luminious Inverter) Battery, efficiency = 85 % DoD = 80 % Solution :  Since , Total Wattage  = 800 W According to saftey Factor = 800 * 1.25 = 1000 Watt Step 1 : Size of inverter =  1 KW Step 2 : Size of Battery: Backup = 3 hour Back up = Total energy / Total wattage Total input energy in battery = 3 * 800 = 2400 wh Output of Battery = 2400 * efficiency = 2400 * 0.80 = 1920 wh if Voltage = 24v, Ah = 1920 / 24 = 80 Ah Charging current of battery = 10 % of Ah = 16 Amp(ideal value)  = 20 amp(real value) 24V, 80V, Step 3 : Solar irradiance in kolkata = 4.12 kwh panel size after losses = 2400 / 0.70 = 3428...

Assignment : How to Design a Solar Power System for home

KISSAN EDUCATION www.kissanedu.com Suppose, Living District = Una, Himachal  Inverter's Efficiency = 95% Battery's Efficiency = 85% Converter Efficiency = 92% Take Loom Solar Panel Inverter = Microtech consider only night backup for battery Solution: Total Day time consumption = 22800 Wh Total Night-Time Consumption = 17280 Wh Total Energy Consumption =  40080 Wh Since Size of Plant is very high, so we have to consider only the night backup plan for optimizing Step 1 : Size of Inverter = Total Wattage of Appliances = Wattage * quantity = 5440 watt = 6 KW inverter Step 2 : Size of Battery: Output Energy of Battery = Input energy of Inverter =(output of inverter) / (efficiency of the inverter)                                           = 17280 /0.95  = 18190 Wh                      ...

Which Year Fossil Fuel (coal,oil & gas) are going to Finish ? | | Explained

KISSAN EDUCATION Visit: ( www.kissanedu.com ) Q. When will approx time that fossil fuel are going to run out from 2003 ? Ans: Lifespan of any Fuel depends upon: What is rate of Production or Reserved of fuel ?  What is rate of consumption ? These Data are Taken from 2003 It means,  after 54 years from 2003, natural gases will Run out i.e.2057  After 205 years from 2003, Coal will Run out i.e.2208  after 54 years from 2003, natural Oil will Run out i.e.2043